Back to Boesch Engineering page
2021 IPC TABLE E103.3(2) LOAD VALUES ASSIGNED TO FIXTURES
Line
Fixture
Occupancy
Type of Supply Control
Cold (wsfu)
Hot (wsfu)
Total (wsfu)
QTY
1
Bathroom group
Private
Flush tank
2.70
1.50
3.60
2
Bathroom group
Private
Flushometer valve
6.00
3.00
8.00
3
Bathtub
Private
Faucet
1.00
1.00
1.40
4
Bathtub
Public
Faucet
3.00
3.00
4.00
5
Bidet
Private
Faucet
1.50
1.50
2.00
6
Combination fixture
Private
Faucet
2.25
2.25
3.00
7
Dishwashing machine
Private
Automatic
0.00
1.40
1.40
8
Drinking fountain
Offices, etc.
3/8in valve
0.25
0.00
0.25
9
Kitchen sink
Private
Faucet
1.00
1.00
1.40
10
Kitchen sink
Hotel restaurant
Faucet
3.00
3.00
4.00
11
Laundry trays (1 to 3)
Private
Faucet
1.00
1.00
1.40
12
Lavatory
Private
Faucet
0.50
0.50
0.70
13
Lavatory
Public
Faucet
1.50
1.50
2.00
14
Service sink
Offices, etc.
Faucet
2.25
2.25
3.00
15
Shower head
Public
Mixing valve
3.00
3.00
4.00
16
Shower head
Private
Mixing valve
1.00
1.00
1.40
17
Urinal
Public
1in flush valve
10.00
0.00
10.00
18
Urinal
Public
3/4in flush valve
5.00
0.00
5.00
19
Urinal
Public
Flush tank
3.00
0.00
3.00
20
Washing machine (8 lb)
Private
Automatic
1.00
1.00
1.40
21
Washing machine (8 lb)
Public
Automatic
2.25
2.25
3.00
22
Washing machine (15 lb)
Public
Automatic
3.00
3.00
4.00
23
Water closet
Private
Flushometer valve
6.00
0.00
6.00
24
Water closet
Private
Flush tank
2.20
0.00
2.20
25
Water closet
Public
Flushometer valve
10.00
0.00
10.00
26
Water closet
Public
Flush tank
5.00
0.00
5.00
27
Water closet
Public or private
Flushometer tank
2.00
0.00
2.00