wws-llc.com

Back to WWS Calculations page


Single Phase Typical Motor FLAs

HP 110-120 Volts 220-240 Volts
1/10 3 1.5
1/8 3.8 1.9
1/6 4.4 2.2
1/4 5.8 2.9
1/3 7.2 3.6
1/2 9.8 4.9
3/4 13.8 6.9
1 16 8
1.5 20 10
2 24 12
3 34 17
5 56 28
7.5 80 40
10 100 50


Three Phase Typical Motor FLAs

HP 208 Volts 220-240 440-480 Volts ---- 200 Volts 380-415 Volts 550-600 Volts
1.2 2.4 2.2 1.1 2.5 1.3 0.9
3/4 3.5 3.2 1.6 3.7 1.8 1.3
1.00 4.6 4.2 2.1 4.8 2.3 1.7
1.5 6.6 6 3 6.9 3.3 2.4
2 7.5 6.8 3.4 7.8 4.3 2.7
3 10.6 9.6 4.8 11 6.1 3.9
5 16.7 15.2 7.6 17.5 9.7 6.1
7.5 24.2 22 11 25.3 14 9
10 30.8 28 14 32.2 18 11
15 46.2 42 21 48.3 27 17
20 59.4 54 27 62.1 34 22
25 74.8 68 34 78.2 44 27
30 88 80 40 92 51 32
40 114 104 52 120 66 41
50 143 130 65 150 83 52
60 169 154 77 177 103 62
75 211 192 96 221 128 77
100 273 248 124 285 165 99
125 343 312 156 359 208 125
150 396 360 180 414 240 144
200 528 480 240 552 320 192
250 - 604 302 - 403 242
300 - 722 361 - 482 289
350 - 828 414 - 560 336
400 - 954 477 - 636 382
450 - 1030 515 - - 412
500 - 1180 590 - 786 472